Product Details
GCS Type Low-Voltage Draw-out Switchgear

Withdrawable switchgear is used in power plants, petrochemical, metallurgical, and light textile industries. It serves as the power distribution (PC) and motor control (MCC) unit for three-phase AC 50-60Hz, 380V power systems.
■Structural Features
- Employs structural components with an E=20mm module for easy assembly.
- Metal structural components are treated with zinc plating or powder coating, providing strong corrosion resistance.
- Compact structure, accommodating multiple functional units in a small space.
- Functional units are separated into several small compartments by steel plates, ensuring no interference between them.
- Functional units utilize three types of structures: drawer, insert, and fixed, making maintenance safe and convenient, and reducing power outage time.
- Drawer operation is simple and convenient, with high interchangeability.
- The drawer is equipped with a mechanism to prevent it from falling due to excessive pulling; the drawer is locked when pulled out to about four-fifths of its length, and requires slight lifting to pull it out completely.
- The cabinet top is equipped with a main busbar and a neutral busbar, and the bottom is equipped with a protective grounding busbar. Four-wire branch busbars are also possible.
- The cable compartment is equipped with brackets for easy cable installation.
■Use Conditions
- Altitude not exceeding 1000m.
- Ambient air temperature not exceeding +40℃; not lower than -25℃.
- Outdoor wind speed not exceeding 35m/s.
- Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%.
- Installation location: Install in a location free from fire, explosion hazards, severe pollution, chemical corrosion, and severe vibration.
- If the above conditions cannot meet the usage requirements, the user may consult with our company.
■ Ordering Instructions
When placing an order, the ordering party should provide the following data related to the product:
- Transformer type and capacity;
- Wiring scheme for the high-voltage and low-voltage compartments, and the type and parameters of selected electrical components;
- Casing color. If the user has no specific requirements, our company’s standard color will be used.
- Any other requirements from the customer can be discussed in person at the time of ordering.
■ Technical Parameters